      <i id='Kalxnv'><tr id='Kalxnv'><dt id='Kalxnv'><q id='Kalxnv'><span id='Kalxnv'><b id='Kalxnv'><form id='Kalxnv'><ins id='Kalxnv'></ins><ul id='Kalxnv'></ul><sub id='Kalxnv'></sub></form><legend id='Kalxnv'></legend><bdo id='Kalxnv'><pre id='Kalxnv'><center id='Kalxnv'></center></pre></bdo></b><th id='Kalxnv'></th></span></q></dt></tr></i><div id='Kalxnv'><tfoot id='Kalxnv'></tfoot><dl id='Kalxnv'><fieldset id='Kalxnv'></fieldset></dl></div>

          <bdo id='Kalxnv'></bdo><ul id='Kalxnv'></ul>

          1. <li id='Kalxnv'><abbr id='Kalxnv'></abbr></li>
          2. 全国销售热线:400-8292-918
            业界新闻
            新闻中心News
            业界新闻
            您当前的位置:皇冠体育竞彩>业界新闻
            冷水机组-冷水机中压缩机过热解决方案
            2017-02-16  来源:互联网转载    发布者:小A

              冷水机在长久的运行当中,压缩机有可能会出现过热故障而导致压缩机无法运行,也就是冷水机出现故障。为了能够认识和解决冷水机的压缩机过热故障,下面,小编将为大家全方位讲解冷水机的压缩机过热问题应对方案。冷水机组,工业冷水机组

              冷冻机的压缩机马达绕组内嵌有热敏电阻,阻值一般为1kΩ。绕组过热时,阻值会迅速增大,超过141kΩ时,热保护模块SSM动作,切断机组运行,同时显示过热故障,TH故障指示灯亮。产生压缩机过热故障的原因如下:冷水机组,工业冷水机组

              第一,压缩机负荷过大,过电流运行。可能的原因是:冷却水温太高、制冷剂充注过多或制冷系统内有空气等不凝结气体,导致压缩机负荷大,表现为过电流,并伴有高压故障。冷水机组,工业冷水机组

              第二,冷冻机的过热保护模块SSM受潮或损坏,中间继电器损坏,触点不良,表现为开机即出现过热故障,压缩机不能启动。如果单元电子板故障或通信故障,也可能假报过热故障。

              第三,电气故障造成冷水机的压缩机过电流运行。如三相电源电压过低或三相不平衡,导致电流或某一相电流过大;交流接触器损坏,触点烧蚀,造成接触电流过大或因缺相而电流过大。

              操作人员如果再次遇到冷冻机的压缩机过热故障时,请参看以上处理方法解决问题。螺杆式冷冻机组,超低温热泵,低温冷水机组

              总之,我们全方位讲解冷水机的压缩机过热问题应对方案就有以上内容,我们要深刻分析和总结,不断掌握新的内容。螺杆式冷冻机组,超低温热泵,低温冷水机组
            冷水机组,工业冷水机组,螺杆式冷冻机组,超低温热泵,低温冷水机组